Assessing Maintenance of Medium Voltage Cable Networks Under Time-Varying Loading

Jochen Lorenz Cremer

Abstract

The electrification and ongoing energy transition lead to systematic changes in electricity loading and variability in power systems. Distribution systems were designed for regular operating patterns, assuming constant low loading. Now, operators need to assess whether their assets can withstand more, as well as time-varying loading. Operating the system at or near its ampacity potentially accelerates thermal ageing, so the question arises: 'how much can one operate at the limits while keeping maintenance and failures low?' This paper introduces a novel approach that derives a time-varying Weibull approximation of failure rates using thermal models and provides a shortcut method to quantify maintenance implications under time-varying loading for heterogeneous MV cable populations. The case studies investigate a dataset from Denmark and the Oberrhein Medium Voltage (MV) system in Germany, studying ageing assets and the interplay with loading, and replacement paradigms of two different cable insulation types. The studies demonstrate that a small fraction of 25% of old, low-quality cables leads to 82% of failures, and 1.4% of the time of highest loading can cause 46% of cable ageing. The case studies also demonstrate that maintenance needs may be between 10-300 times higher under future loading conditions associated with the energy transition, specifically in networks that have older PILC cables. This paper provides a new tool for operators to plan maintenance under more realistic, future operating conditions.

Assessing Maintenance of Medium Voltage Cable Networks Under Time-Varying Loading

Abstract

The electrification and ongoing energy transition lead to systematic changes in electricity loading and variability in power systems. Distribution systems were designed for regular operating patterns, assuming constant low loading. Now, operators need to assess whether their assets can withstand more, as well as time-varying loading. Operating the system at or near its ampacity potentially accelerates thermal ageing, so the question arises: 'how much can one operate at the limits while keeping maintenance and failures low?' This paper introduces a novel approach that derives a time-varying Weibull approximation of failure rates using thermal models and provides a shortcut method to quantify maintenance implications under time-varying loading for heterogeneous MV cable populations. The case studies investigate a dataset from Denmark and the Oberrhein Medium Voltage (MV) system in Germany, studying ageing assets and the interplay with loading, and replacement paradigms of two different cable insulation types. The studies demonstrate that a small fraction of 25% of old, low-quality cables leads to 82% of failures, and 1.4% of the time of highest loading can cause 46% of cable ageing. The case studies also demonstrate that maintenance needs may be between 10-300 times higher under future loading conditions associated with the energy transition, specifically in networks that have older PILC cables. This paper provides a new tool for operators to plan maintenance under more realistic, future operating conditions.

Paper Structure

This paper contains 26 sections, 48 equations, 18 figures, 2 tables.

Figures (18)

  • Figure 1: Failures of medium voltage cables in Denmark. The increase is due to age-related failure (applied from Sun25Han23Den23).
  • Figure 2: The annual cable utilisation for three energy scenarios (applied from Fig. 10 inZap21).
  • Figure 3: Oberrhein MV network with PILC and XLPE cables.
  • Figure 4: Loading of the Oberrhein MV grid. (a) Mean load at buses over a $24$-hour period. (b) Line loading (in %) relative to the maximum loading and limit loading.
  • Figure 5: XLPE
  • ...and 13 more figures